aboutsummaryrefslogtreecommitdiff
path: root/electrical-specifications.typ
diff options
context:
space:
mode:
Diffstat (limited to 'electrical-specifications.typ')
-rw-r--r--electrical-specifications.typ55
1 files changed, 30 insertions, 25 deletions
diff --git a/electrical-specifications.typ b/electrical-specifications.typ
index fcc6f7c..c4416fe 100644
--- a/electrical-specifications.typ
+++ b/electrical-specifications.typ
@@ -188,8 +188,8 @@ achievable with a standard HVAC.
===== Humidity <humidity>
Measurements are made within a relative humidity range of
-$qtyrange(30, 70, "percent", delimiter: "\"to\"") "RH"$, with an hourly
-variation of maximum $plus.minus qty(5, "percent") "RH"$.
+$qtyrange(30, 70, "percent", delimiter: "\"to\"") upright("RH")$, with an hourly
+variation of maximum $plus.minus qty(5, "percent") upright("RH")$.
High humidity can cause parasitic leakage paths (nanoamps matter at high-Z
nodes), dielectric changes affecting precision capacitors, and long-term
@@ -216,9 +216,9 @@ to $qty(2000, "m")$ altitude, under normal atmospheric conditions.
===== Electro-magnetic environment <electro-magnetic-environment>
RF field immunity must follow EN 61000-4-3 specification (
-$qty(3, "volt per meter")$, $qtyrange(80, 1000, "MHz")$). The magnetic field
-should be below $qty(1, "ampere per meter") "DC"$, and below
-$qty(0.3, "ampere per meter") "AC"$ (power frequency). SAME equipment should be
+$qty(3, "volt per meter")$, $qtyrange(80, 1000, "MHz", delimiter: "\"to\"")$). The magnetic field
+should be below $qty(1, "ampere per meter", per: "/") upright("DC")$, and below
+$qty(0.3, "ampere per meter", per: "/") upright("AC")$ (power frequency). SAME equipment should be
at least $qty(1, "m")$ away from switching equipment such as motors, welders
etc.
@@ -243,7 +243,7 @@ SAME equipment should be operated on stable surfaces, free from significant
vibration. Vibration can induce microphonic effects in capacitors and
connectors, affecting precision at high-impedance nodes.
-Operating vibration should be below $qty(0.5, "g")$ ($qtyrange(5, 500, "Hz")$).
+Operating vibration should be below $qty(0.5, "g")$ ($qtyrange(5, 500, "Hz", delimiter: "\"to\"")$).
Shock should be below $qty(5, "g")$ ($qty(11, "ms")$ pulse).
These requirements should be met in normal laboratory or studio environments.
@@ -260,7 +260,7 @@ cassettes removed in bright light.
===== Ionizing radiation <ionizing-radiation>
SAME is designed for normal background radiation environments (below
-$qty(1, "micro sievert per hour")$).
+$qty(1, "micro sievert per hour", per: "/")$).
Operation near significant ionizing radiation sources such as medical imaging
equipment, nuclear facilities, or particle accelerators is not recommended
@@ -297,19 +297,21 @@ are met.
table(
columns: 3,
table.header([Parameter], [Range], [Variation]),
- [Temperature], [$plus qty(15, "dC") "to" plus qty(30, "dC")$], [$plus.minus qty(2, "celsius per hour")$],
+ [Temperature], [$plus qty(15, "dC") "to" plus qty(30, "dC")$], [$plus.minus qty(2, "celsius per hour", per: "/")$],
[Relative humidity],
[$qtyrange(30, 79, "percent", delimiter: "\"to\"") "RH"$],
[$plus.minus qty(5, "percent") "RH"$],
- [Atmospheric pressure], [$qtyrange(800, 1100, "hPa")$], [$plus.minus qty(50, "hecto pascal per day")$],
+ [Atmospheric pressure],
+ [$qtyrange(800, 1100, "hPa", delimiter: "\"to\"")$],
+ [$plus.minus qty(50, "hecto pascal per day", per: "/")$],
- [RF immunity], [$qty(3, "volt per meter"), qtyrange(80, 1000, "MHz")$], [N/A],
+ [RF immunity], [$qty(3, "volt per meter", per: "/"), qtyrange(80, 1000, "MHz", delimiter: "\"to\"")$], [N/A],
- [Magnetic field (DC)], [$lt qty(1, "ampere per meter")$], [N/A],
+ [Magnetic field (DC)], [$lt qty(1, "ampere per meter", per: "/")$], [N/A],
- [Magnetic field (AC)], [$lt qty(0.3, "ampere per meter")$], [N/A],
+ [Magnetic field (AC)], [$lt qty(0.3, "ampere per meter", per: "/")$], [N/A],
[Vibration], [$lt qty(0.5, "g"), qtyrange(5, 500, "Hz")$], [N/A],
@@ -319,7 +321,7 @@ are met.
[Lighting], [No direct sunlight], [N/A],
- [Background radiation], [$lt qty(1, "micro sievert per hour")$], [N/A],
+ [Background radiation], [$lt qty(1, "micro sievert per hour", per: "/")$], [N/A],
),
caption: [Summary of the precision measurements conditions],
) <table-precision-measurements-conditions-summary>
@@ -335,7 +337,7 @@ entry by reducing the components costs and soldering difficulty. It is suitable
for teaching on circuit topologies and general analog computer patching. At this
level of precision, results are valid within $plus.minus qty(10, "mV")$.
-The maximum drift rate should be inferior or equal to $qty(60, "ppm per hour")$.
+The maximum drift rate should be inferior or equal to $qty(60, "ppm per hour", per: "/")$.
We recommend calibration verification before each session.
=== Industrial tier <industrial-tier>
@@ -348,7 +350,7 @@ acquisition. At this level of precision, results are valid within
$plus.minus qty(1, "mV")$.
The maximum drift rate should be inferior or equal to
-$qty(0.6, "ppm per hour")$. We recommend daily calibration verification.
+$qty(0.6, "ppm per hour", per: "/")$. We recommend daily calibration verification.
=== Metrologic tier <metrologic-tier>
@@ -360,7 +362,7 @@ operation. At this level of precision, results are valid within
$plus.minus qty(0.1, "mV")$.
The maximum drift rate should be inferior or equal to
-$qty(0.014, "ppm per hour")$. We recommend daily calibration verification.
+$qty(0.014, "ppm per hour", per: "/")$. We recommend daily calibration verification.
=== Summary <precision-tiers-summary>
@@ -377,7 +379,10 @@ $qty(0.014, "ppm per hour")$. We recommend daily calibration verification.
[Result validity], [$plus.minus qty(0.1, "V")$], [$plus.minus qty(10, "mV")$], [$plus.minus qty(1, "mV")$],
- [Maximum drift rate], [$qty(60, "ppm per hour")$], [$qty(0.6, "ppm per hour")$], [$qty(0.014, "ppm per hour")$],
+ [Maximum drift rate],
+ [$qty(60, "ppm per hour", per: "/")$],
+ [$qty(0.6, "ppm per hour", per: "/")$],
+ [$qty(0.014, "ppm per hour", per: "/")$],
[Drift-free computation], [$approx qty(16, "h")$], [$approx qty(7, "day")$], [$approx qty(30, "day")$],
@@ -396,11 +401,11 @@ the precision budget.
table(
columns: 4,
table.header([Tier], [Precision], [Drift rate], [Time to drift $qty(100, "percent")$ of budget]),
- [*Educational*], [$qty(1000, "ppm")$], [$qty(60, "ppm per hour")$], [$approx qty(16, "h")$],
+ [*Educational*], [$qty(1000, "ppm")$], [$qty(60, "ppm per hour", per: "/")$], [$approx qty(16, "h")$],
- [*Industrial*], [$qty(100, "ppm")$], [$qty(0.6, "ppm per hour")$], [$approx qty(7, "day")$],
+ [*Industrial*], [$qty(100, "ppm")$], [$qty(0.6, "ppm per hour", per: "/")$], [$approx qty(7, "day")$],
- [*Metrologic*], [$qty(10, "ppm")$], [$qty(0.014, "ppm per hour")$], [$approx qty(30, "day")$],
+ [*Metrologic*], [$qty(10, "ppm")$], [$qty(0.014, "ppm per hour", per: "/")$], [$approx qty(30, "day")$],
),
caption: [Drift rate derivations],
) <table-drift-rate-derivation>
@@ -501,10 +506,10 @@ noise shall not exceed $qty(5, "mVpp")$ over a $qty(20, "MHz")$ bandwidth.
The $plus.minus qty(10.0000, "V")$ reference rails shall maintain an initial
accuracy within $plus.minus qty(20, "uV")$ ($plus.minus qty(2, "ppm")$) at
$qty(25, "dC")$. Line regulation shall be strictly less than
-$qty(2, "micro volt per volt")$ ($qty(0.2, "ppm per volt")$). Load regulation
-shall be strictly less than $qty(5, "micro volt per milli ampere")$
-($qty(0.5, "ppm per milli ampere")$). The temperature coefficient must be less
-than $qty(0.5, "ppm per celsius")$, and low-frequency noise
+$qty(2, "micro volt per volt", per: "/")$ ($qty(0.2, "ppm per volt", per: "/")$). Load regulation
+shall be strictly less than $qty(5, "micro volt per milli ampere", per: "/")$
+($qty(0.5, "ppm per milli ampere", per: "/")$). The temperature coefficient must be less
+than $qty(0.5, "ppm per celsius", per: "/")$, and low-frequency noise
($qtyrange(0.1, 10, "Hz", delimiter: "\"to\"")$) shall not exceed
$qty(2, "uVpp")$.
@@ -513,7 +518,7 @@ $qty(2, "uVpp")$.
The $qty(10, "MHz")$ Master Oscillator shall demonstrate frequency stability
inferior or equal to $qty(10, "ppb")$ (parts per billion) over the full
operating temperature range. Phase noise shall be inferior or equal to
-$qty(-140, "dBc per Hz")$ at a $qty(1, "kHz")$ offset.
+$qty(-140, "dBc per Hz", per: "/")$ at a $qty(1, "kHz")$ offset.
===== Grounding rules <grounding-rules>